withdrawable circuit breaker, without guide frame, IEC 60947-2, size 2, 4-pole, N pole on right, In=2500 A, breaking capacity E, without internal voltage tap up to 1150 V AC 50/60 Hz, Icu=85/70 kA at 1000/1150 V, ETU600 LSIG electronic trip unit upgradeable, color display, Bluetooth, USB interface, basic protection LT, ST, INST, GFx, including protection of the N conductor (internal neutral point sensor available), trip alarm switch (1 x CO), guide frame with shutter, without position signaling switch